TCO2C-NTC20 CO 2 transmitter, air duct mounting

CO2 + NTC 20, 20 kOhm (25°C)

Specifications

Specifications for TCO2C-NTC20
Sensor Interface Passive, 0-10 V
Display No
Tube length 23 cm
Insertion length 60…230 mm
Measuring range, temp 0…50 °C
Output signal, gas in air 0-10 V
Accuracy, gas in air < ± (50 ppm + 2 % of the measured value) (25 °C)
Warm-up time < 5 min
Temperature dependance Typically 5 ppm / K
Specifications for CO2 transmitter, air duct mounting
Power Supply 24VAC/DC (22...26 V AC 50/60Hz / 15...35 V DC), VA
Appliance class Class III
Protection class IP30
Ambient humidity (non-condensing) 10…90 % RH
Ambient temperature 0…50 °C
Storage temperature -25…60 °C
Mounting Duct
Dimensions, external (WxHxD) 75x77x36 mm
Tube diameter 12 mm
Accuracy, temperature 0.2 K
Measuring range, gas in air 0…2000 ppm
Response time < 90 sec
Long term stability Typically 20 ppm / year
Terminal type Screw Terminal
Terminal wire size 1.5 mm²
Material, housing Polycarbonate
Power consumption < 2.5 W
Transformer power 5 VA

Accessories

You´re on Italy site
Change language? English italiano (Italia)
Change sales company?
Austria (Redirect to: regincontrols.com) Benelux (Redirect to: regincontrols.com) Denmark (Redirect to: regincontrols.com) France (Redirect to: regincontrols.com) Germany (Redirect to: regincontrols.com) International (Redirect to: regincontrols.com) Sweden (Redirect to: regincontrols.com) Switzerland (Redirect to: regincontrols.com)