Specifications for TPDA
Sensor Interface 0-10 V, 4-20 mA
Display Yes
Display type LED, three digits
Analogue output load impedance 0...10v >2 kΩ
Analogue output load impedance 4...20mA 500 Ω
Measuring range pressure 0...100 / 0...300 / 0...500 / 0...999 Pa, selectable
Media air or not aggressive gases
Accuracy, pressure sensor 1 ± 1% at 20 °C %
Max. allowed diff. Pressure sensor 1 20 kPa
Specifications for Differential pressure transmitter with display
Power Supply 24VAC/DC (22...26 V AC 50Hz / 22...26 V DC), 5.0 VA
Protection class IP54
Ambient humidity (non-condensing) 0…90 % RH
Ambient temperature 0…50 °C
Storage temperature -40…50 °C
Mounting Wall
Dimensions, external (WxHxD) 129x89x58 mm
Analogue outputs type (AO) 0...10 V DC
Damping (electronic) 0...20 s
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 1.5 mm²
You´re on Italy site
Change language? English italiano (Italia)
Change sales company?
Austria (Redirect to: regincontrols.com) Benelux (Redirect to: regincontrols.com) Denmark (Redirect to: regincontrols.com) France (Redirect to: regincontrols.com) Germany (Redirect to: regincontrols.com) International (Redirect to: regincontrols.com) Sweden (Redirect to: regincontrols.com) Switzerland (Redirect to: regincontrols.com)