Industrietechnik

Duct humidity/temperature transmitter

Designed for accurate measurement of carbon dioxide concentration, relative humidity, and temperature in air within duct systems, ensuring optimal performance and accuracy for enhanced indoor air quality monitoring. Reliable and easy to install, ideal for use in HVAC systems across residential, commercial, and industrial applications. Available with Modbus RTU or analog 0-10 V output.

Articles

(4 st)
  • TCV1101 - Regin
    TCV1101
    Tube length
    23 cm
    Insertion length
    100…230 mm
    Analogue output load impedance 0...10v
    >10 kΩ
    Measuring range, temp
    -20…70 °C
    Output temperature
    0-10 V
    Output humidity
    0-10 V
    Output signal, gas in air
    0-10 V
    Accuracy, gas in air
    ±(30 ppm +3%) @25°C
    Colour, cover
    White (RAL 9010)
    Colour, base
    Gray (RAL 7038)
  • TCM1001 - Regin
    TCM1001
    Tube length
    23 cm
    Insertion length
    100…230 mm
    Analogue output load impedance 0...10v
    >10 kΩ
    Measuring range, temp
    -20…70 °C
    Output temperature
    Modbus
    Output humidity
    Modbus
    Colour, cover
    White (RAL 9010)
    Colour, base
    Gray (RAL 7038)
  • TCM0101 - Regin
    TCM0101
    Tube length
    23 cm
    Insertion length
    100…230 mm
    Analogue output load impedance 0...10v
    >10 kΩ
    Measuring range, temp
    -20…70 °C
    Output temperature
    Modbus
    Output signal, gas in air
    Modbus
    Accuracy, gas in air
    ±(30 ppm +3%) @25°C
    Colour, cover
    White (RAL 9010)
    Colour, base
    Gray (RAL 7038)
  • TCM1101 - Regin
    TCM1101
    Tube length
    23 cm
    Insertion length
    100…230 mm
    Analogue output load impedance 0...10v
    >10 kΩ
    Measuring range, temp
    -20…70 °C
    Output temperature
    Modbus
    Output humidity
    Modbus
    Output signal, gas in air
    Modbus
    Accuracy, gas in air
    ±(30 ppm +3%) @25°C
    Colour, cover
    White (RAL 9010)
    Colour, base
    Gray (RAL 7038)

Specifications

Specifications for Duct humidity/temperature transmitter
Appliance class Class III
Protection class IP65
Ambient humidity (non-condensing) 10…90 % RH
Ambient temperature 0…50 °C
Storage temperature -20…70 °C
Mounting Duct
Dimensions, external (WxHxD) 75x103x266 mm
Weight, incl. packaging 0.26 kg
Tube diameter 12 mm
Accuracy, temperature 0.4 @25°C K
Measuring range, humidity 0…100 % RH
Accuracy, humidity ± 3% RH @20°C
Measuring range, gas in air 0…2000 ppm
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 0.75 mm²
Material, housing ABS according to UL94 V-0
Power consumption < 2.5 W
Power supply 24 Vac ±10% / 16...35 Vdc