Industrietechnik

Clamp-on sensor with cable

For surface temperature measurement. Including clamp (Ø max 40 mm).

Articles

(10 st)
  • SCC-PT100 - Regin
    SCC-PT100
    Clamp-on sensor, including clamp (Ø 40 mm max.)
    Mounting
    Clamp-on
    Dimensions, external (WxHxD)
    10x7x35 mm
    Cable length
    1.5 m
    Measuring range, temp
    -30…150 °C
    Element type
    PT100
    Nominal resistance
    100 Ω @0°C, Class B
  • SCC-PT1000 - Regin
    SCC-PT1000
    Clamp-on sensor, including clamp (Ø 40 mm max.)
    Mounting
    Clamp-on
    Dimensions, external (WxHxD)
    10x7x35 mm
    Cable length
    1.5 m
    Measuring range, temp
    -30…150 °C
    Element type
    PT1000
    Nominal resistance
    1000 Ω @0°C, Class B
  • SCC-NTC1.8 - Regin
    SCC-NTC1.8
    Clamp-on sensor, including clamp (Ø 40 mm max.)
    Mounting
    Clamp-on
    Dimensions, external (WxHxD)
    10x7x35 mm
    Cable length
    1.5 m
    Element type
    NTC1.8
    Measuring range, temp
    -30…120 °C
    Nominal resistance
    1800 Ω @25°C, Beta 3416
    Equivalent
    TAC
  • SCC-NTC2.2 - Regin
    SCC-NTC2.2
    Clamp-on sensor, including clamp (Ø 40 mm max.)
    Mounting
    Clamp-on
    Dimensions, external (WxHxD)
    10x7x35 mm
    Cable length
    1.5 m
    Element type
    NTC2.2
    Measuring range, temp
    -30…150 °C
    Nominal resistance
    2252 Ω @25°C, Beta 3977
    Equivalent
    Johnson Controls
  • SCC-NTC10-01 - Regin
    SCC-NTC10-01
    Clamp-on sensor, including clamp (Ø 40 mm max.)
    Mounting
    Clamp-on
    Dimensions, external (WxHxD)
    10x7x35 mm
    Media temp limits
    -30…150 °C
    Cable length
    1.5 m
    Time constant
    13 s
    Element type
    NTC10-01
    Measuring range, temp
    -30…150 °C
    Nominal resistance
    10 kΩ @25°C, Beta 3977
    Equivalent
    Aquatrol - Johnson Controls - Satchwell - Trend - Cylon - Honeywell
  • SCC-NTC10-02-BR-J - Regin
    SCC-NTC10-02-BR-J
    Mounting
    Clamp-on
    Cable length
    2 m
    Element type
    NTC10-02
    Measuring range, temp
    -50…110 °C
    Nominal resistance
    10 kΩ @25°C, Beta 3435
    Equivalent
    Carel - Evco - Eliwell - AB Industrietechnik
  • SCC-NTC10-03 - Regin
    SCC-NTC10-03
    Clamp-on sensor, including clamp (Ø 40 mm max.)
    Mounting
    Clamp-on
    Dimensions, external (WxHxD)
    10x7x35 mm
    Media temp limits
    -30…150 °C
    Cable length
    1.5 m
    Time constant
    13 s
    Element type
    NTC10-03
    Measuring range, temp
    -30…150 °C
    Nominal resistance
    10 kΩ @25°C, Beta 3695
    Equivalent
    Andover - Delta Controls - Siebe - York
  • SCC-NTC15-01 - Regin
    SCC-NTC15-01
    Clamp-on sensor, including clamp (Ø 40 mm max.)
    Mounting
    Clamp-on
    Cable length
    1.5 m
    Element type
    NTC15
    Measuring range, temp
    0…30 °C
    Nominal resistance
    15 kΩ @0°C
    Equivalent
    Regin - AB Industrietechnik
  • SCC-NI1000-01 - Regin
    SCC-NI1000-01
    Clamp-on sensor, including clamp (Ø 40 mm max.)
    Mounting
    Clamp-on
    Dimensions, external (WxHxD)
    10x7x35 mm
    Cable length
    1.5 m
    Element type
    NI1000-01
    Measuring range, temp
    -30…150 °C
    Nominal resistance
    1000 Ω @0°C, TK5000
    Equivalent
    Siemens - Landis & Staefa
  • SCC-NI1000-02 - Regin
    SCC-NI1000-02
    Clamp-on sensor, including clamp (Ø 40 mm max.)
    Mounting
    Clamp-on
    Dimensions, external (WxHxD)
    10x7x35 mm
    Cable length
    1.5 m
    Element type
    NI1000-02
    Measuring range, temp
    -30…150 °C
    Nominal resistance
    1000 Ω @0°C, TK6180
    Equivalent
    Sauter

Specifications

Specifications for Clamp-on sensor with cable
Protection class IP65
Media Clamp-on sensor with cable for mounting on pipe
Material sensor Nickel plated copper, Nickel-plated copper tube, Plastic rubber
Material cable Silicone
Mounting: Sul tubo con fascetta

Accessories