Industrietechnik

Outdoor temperature sensor with housing

Outdoor sensor for air temperature measurement. The sensors are compatible with a wide range of control systems, including Aquatrol, Johnson Controls, Satchwell, Trend, Cylon, Honeywell and many others. Contact our sales team to choose the model best suited to your application.

Articles

(9 st)
  • SE-PT100-Y - Regin
    SE-PT100-Y
    Outdoor sensor
    Mounting
    Outdoor
    Dimensions, external (WxHxD)
    78x51x104 mm
    Media temp limits
    -50…70 °C
    Measuring range, temp
    -50…70 °C
    Element type
    PT100
    Nominal resistance
    100 Ω @0°C, Class B
  • SE-PT1000-Y - Regin
    SE-PT1000-Y
    Outdoor sensor
    Mounting
    Outdoor
    Dimensions, external (WxHxD)
    78x51x104 mm
    Media temp limits
    -50…70 °C
    Measuring range, temp
    -50…70 °C
    Element type
    PT1000
    Nominal resistance
    1000 Ω @0°C, Class B
  • SE-NTC2.2-Y - Regin
    SE-NTC2.2-Y
    Outdoor sensor
    Mounting
    Outdoor
    Dimensions, external (WxHxD)
    78x51x104 mm
    Media temp limits
    -50…70 °C
    Measuring range, temp
    -50…70 °C
    Element type
    NTC2.2
    Nominal resistance
    1800 Ω @25°C, Beta 3416
    Equivalent
    TAC
  • SE-NTC10-01-Y - Regin
    SE-NTC10-01-Y
    Outdoor sensor
    Mounting
    Outdoor
    Dimensions, external (WxHxD)
    78x51x104 mm
    Media temp limits
    -50…70 °C
    Measuring range, temp
    -50…70 °C
    Element type
    NTC10-01
    Nominal resistance
    10 kΩ @25°C, Beta 3977
    Equivalent
    Aquatrol - Johnson Controls - Satchwell - Trend - Cylon - Honeywell - Distech
  • SE-NTC10-02-Y - Regin
    SE-NTC10-02-Y
    Outdoor sensor
    Mounting
    Outdoor
    Dimensions, external (WxHxD)
    78x51x104 mm
    Media temp limits
    -50…70 °C
    Measuring range, temp
    -50…70 °C
    Element type
    NTC10-02
    Nominal resistance
    10 kΩ @25°C, Beta 3435
    Equivalent
    Carel - Evco - Eliwell - AB Industrietechnik
  • SE-NTC10-03-Y - Regin
    SE-NTC10-03-Y
    Outdoor sensor
    Mounting
    Outdoor
    Dimensions, external (WxHxD)
    78x51x104 mm
    Media temp limits
    -50…70 °C
    Measuring range, temp
    -50…70 °C
    Element type
    NTC10-03
    Nominal resistance
    10 kΩ @25°C, Beta 3695
    Equivalent
    Andover - Delta Controls - Siebe - York
  • SE-NTC20-Y - Regin
    SE-NTC20-Y
    Outdoor sensor
    Mounting
    Outdoor
    Dimensions, external (WxHxD)
    78x51x104 mm
    Media temp limits
    -50…70 °C
    Measuring range, temp
    -50…70 °C
    Element type
    NTC20
    Nominal resistance
    20 kΩ @25°C, Beta 4262
    Equivalent
    Honeywell
  • SE-NI1000-01-Y - Regin
    SE-NI1000-01-Y
    Outdoor sensor
    Mounting
    Outdoor
    Dimensions, external (WxHxD)
    78x51x104 mm
    Media temp limits
    -50…70 °C
    Measuring range, temp
    -50…70 °C
    Element type
    NI1000-01
    Nominal resistance
    1000 Ω @0°C, TK5000
    Equivalent
    Siemens - Landis & Staefa
  • SE-NI1000-02-Y - Regin
    SE-NI1000-02-Y
    Outdoor sensor
    Mounting
    Outdoor
    Dimensions, external (WxHxD)
    78x51x104 mm
    Media temp limits
    -50…70 °C
    Measuring range, temp
    -50…70 °C
    Element type
    NI1000-02
    Nominal resistance
    1000 Ω @0°C, TK6180
    Equivalent
    Siemens - Landis & Staefa

Specifications

Specifications for Outdoor temperature sensor with housing
Protection class IP65
Mounting Wall
Cable gland M16x1,5
Terminal type Screw Terminal
Terminal wire size 1.5 mm²
Material, housing Polycarbonate (PC)
Material, base Polycarbonate (PC)