Industrietechnik
Discontinued - CO2 transmitter, air duct mounting
Measures the concentration of carbon dioxide in ducts. Exempt from periodic calibration. Discontinued products The TCOC series are respaced with new series TCO2C. Discontinued productsThe TCOC series are respaced with new series TCO2C.
Navigate on this page
Articles
(1 st)-
TCOC1111
- Temperature range
- -5…+50 °C
- CO 2 range
- 0…2000 ppm
- Output, temperature
- NTC10-02
- Output, CO 2
- 0…10 V DC
Specifications
Supply voltage | 24…35 V DC / 24 V AC ± 10% 50-60 Hz |
---|---|
Power consumption | 1.3 VA (<1 W), 12 VA for 0.3 s every 15 s |
Output voltage | 0…10 V DC or 0…5 VDC, R L > 1 kOhm |
Temperature sensors | NTC 10K |
CO 2 sensor | NDIR sensor accuracy ± (50 ppm + 2% of value) time stability ± 20 ppm / year CO 2 sampling 15 s max air speed 10 m / s |
Ambient temperature | -5…+50°C |
Ambient humidity | 10…90 % RH (non-condensing) |
Storage temperature | -20…+70°C |
TC dependence | 2 ppm CO 2 / °C |
Casing | base in ABS, PC transparent cover |
Weight | 190 g |
Dimensions | 140 x 62 x 65mm |
Protection class | IP65 |
Accessories
DBZ-22
Mounting bracket for air duct transmitters