Damper actuators without spring return, 24 Nm

Well-suited for applications with dampers (6 m2) in ventilation and air handling units.

Articles

(8 st)
  • DAL24 - Regin
    DAL24
    Dimensions, external (WxHxD)
    100*180*67 mm
    Supply voltage
    24 V AC/DC
    Torque
    24 Nm
    Control signal
    2 - 3 point
    Running time, actuator
    125 s
    Damper shaft, round
    10…20mm mm
    Damper shaft, square
    10…16mm mm
    Damper shaft, min shaft length
    50 mm
    Max damper size (area)
    6 m²
    Frequency
    50...60 Hz
    Power consumption in operation
    3.9 W
    Power consumption in rest position
    0.4 W
    Power consumption for wire sizing
    4.1 VA
    Angle limitation
    5...85° in 5° steps
  • DAL24S - Regin
    DAL24S
    Dimensions, external (WxHxD)
    100*180*67 mm
    Supply voltage
    24 V AC/DC
    Torque
    24 Nm
    Control signal
    2 - 3 point
    Running time, actuator
    125 s
    Auxiliary switch
    Yes
    Damper shaft, round
    10…20mm mm
    Damper shaft, square
    10…16mm mm
    Damper shaft, min shaft length
    50 mm
    Max damper size (area)
    6 m²
    Frequency
    50...60 Hz
    Power consumption in operation
    3.9 W
    Power consumption in rest position
    0.4 W
    Power consumption for wire sizing
    4.1 VA
    Angle limitation
    5...85° in 5° steps
  • DAL230 - Regin
    DAL230
    Dimensions, external (WxHxD)
    100*180*67 mm
    Supply voltage
    230 V AC/DC
    Torque
    24 Nm
    Control signal
    2 - 3 point
    Running time, actuator
    125 s
    Damper shaft, round
    10…20mm mm
    Damper shaft, square
    10…16mm mm
    Damper shaft, min shaft length
    50 mm
    Max damper size (area)
    6 m²
    Frequency
    50...60 Hz
    Power consumption in operation
    4.8 W
    Power consumption in rest position
    1.2 W
    Power consumption for wire sizing
    4.1 VA
    Angle limitation
    5...85° in 5° steps
  • DAL230S - Regin
    DAL230S
    Dimensions, external (WxHxD)
    100*180*67 mm
    Supply voltage
    230 V AC/DC
    Torque
    24 Nm
    Control signal
    2 - 3 point
    Running time, actuator
    125 s
    Auxiliary switch
    Yes
    Damper shaft, round
    10…20mm mm
    Damper shaft, square
    10…16mm mm
    Damper shaft, min shaft length
    50 mm
    Max damper size (area)
    6 m²
    Frequency
    50...60 Hz
    Power consumption in operation
    4.8 W
    Power consumption in rest position
    1.2 W
    Power consumption for wire sizing
    4.1 VA
    Angle limitation
    5...85° in 5° steps
  • DML24 - Regin
    DML24
    Dimensions, external (WxHxD)
    100*180*67 mm
    Supply voltage
    24 V AC/DC
    Torque
    24 Nm
    Control signal
    Y1: 0(2)...10 V DC
    Feedback signal
    U: 0(2)...10 V DC
    Running time, actuator
    125 s
    Damper shaft, round
    10…20mm mm
    Damper shaft, square
    10…16mm mm
    Damper shaft, min shaft length
    50 mm
    Max damper size (area)
    6 m²
    Frequency
    50...60 Hz
    Power consumption in operation
    4.0 W
    Power consumption in rest position
    0.7 W
    Power consumption for wire sizing
    4.1 VA
    Angle limitation
    5...85° in 5° steps
  • DML24S - Regin
    DML24S
    Dimensions, external (WxHxD)
    100*180*67 mm
    Supply voltage
    24 V AC/DC
    Torque
    24 Nm
    Control signal
    Y1: 0(2)...10 V DC
    Feedback signal
    U: 0(2)...10 V DC
    Running time, actuator
    125 s
    Auxiliary switch
    Yes
    Damper shaft, round
    10…20mm mm
    Damper shaft, square
    10…16mm mm
    Damper shaft, min shaft length
    50 mm
    Max damper size (area)
    6 m²
    Frequency
    50...60 Hz
    Power consumption in operation
    4.0 W
    Power consumption in rest position
    0.7 W
    Power consumption for wire sizing
    4.1 VA
    Angle limitation
    5...85° in 5° steps
  • DML230 - Regin
    DML230
    Dimensions, external (WxHxD)
    100*180*67 mm
    Supply voltage
    230 V AC
    Torque
    24 Nm
    Control signal
    Y1: 0(2)...10 V DC
    Feedback signal
    U: 0(2)...10 V DC
    Running time, actuator
    125 s
    Damper shaft, round
    10…20mm mm
    Damper shaft, square
    10…16mm mm
    Damper shaft, min shaft length
    50 mm
    Max damper size (area)
    6 m²
    Frequency
    50...60 Hz
    Power consumption in operation
    4.0 W
    Power consumption in rest position
    0.7 W
    Power consumption for wire sizing
    4.1 VA
    Angle limitation
    5...85° in 5° steps
  • DML230S - Regin
    DML230S
    Dimensions, external (WxHxD)
    100*180*67 mm
    Supply voltage
    230 V AC
    Torque
    24 Nm
    Control signal
    Y1: 0(2)...10 V DC
    Feedback signal
    U: 0(2)...10 V DC
    Running time, actuator
    125 s
    Auxiliary switch
    Yes
    Damper shaft, round
    10…20mm mm
    Damper shaft, square
    10…16mm mm
    Damper shaft, min shaft length
    50 mm
    Max damper size (area)
    6 m²
    Frequency
    50...60 Hz
    Power consumption in operation
    4.0 W
    Power consumption in rest position
    0.7 W
    Power consumption for wire sizing
    4.1 VA
    Angle limitation
    5...85° in 5° steps

Specifications

Specifications for Damper actuators without spring return, 24 Nm
Appliance class Class III
Protection class IP44
Protection class, additional information IP54 with cable glands
Ambient humidity (non-condensing) 5…95 % RH
Ambient temp -20…50 °C
Weight, incl. packaging 1.1 kg
Working angle, rotation 90 °