Industrietechnik
TCO2A-NTC10-01 Room-mounted temperature and CO₂ transmitter
CO2 + NTC 10, 10 kOhm (25°C)
Specifications
| Display | No |
|---|---|
| Output signal | 0…10 V + ohm |
| Accuracy, temperature | ± 0.2 °C |
| Supply voltage | 24 V AC ±10 %, 50...60 Hz / 15...35 V DC |
|---|---|
| Working range, CO 2 | 0…2000ppm |
| Working range, temperature | 0…50°C |
| Working range, humidity | 10…90% RH |
| Power consumption | < 2.5 W |
| Energy consumption | < 0.5 Wh |
| Transformer power | ≥ 5 VA |
| Accuracy, CO 2 | < ± (50 ppm + 2 % of the measured value) (25 °C) |
| Accuracy, humidity | ±3 % RH (20°C) |
| Mounting | Room |
| Dimensions | 100 x 85 x 30.5mm |
| Protection class | IP30 |
| CO 2 | 0...10 V DC referring to 0...2000 ppm |
| Temperature | 0...10 V DC referring to 0…50°C |
| Humidity | 0...10 V DC referring to 0...100 % RH |
Software & documentation
Product sheet
Instructions
Other documentation