Industrietechnik
Immersion sensor with housing, without well, R1/4"
Immersion sensor for temperature measurement of heating or cooling batteries in ventilation units. Probe in stainless steel without a well. The sensors are compatible with a wide range of control systems, including Aquatrol, Johnson Controls, Satchwell, Trend, Cylon, Honeywell and many others. Contact our sales team to choose the model best suited to your application.
Articles
(10 st)-
SI-PT100-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -20…120 °C
- Element type
- PT100
- Nominal resistance
- 100 Ω @0°C, Class B
- Insertion length
- 90 mm
-
SI-PT1000-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -20…120 °C
- Element type
- PT1000
- Nominal resistance
- 1000 Ω @0°C, Class B
- Insertion length
- 90 mm
-
SI-NTC1.8-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -20…120 °C
- Element type
- NTC1.8
- Nominal resistance
- 1800 Ω @25°C, Beta 3416
- Equivalent
- TAC
- Insertion length
- 90 mm
-
SI-NTC2.2-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -20…120 °C
- Element type
- NTC2.2
- Nominal resistance
- 2252 Ω @25°C, Beta 3977
- Equivalent
- Johnson Controls
- Insertion length
- 90 mm
-
SI-NTC10-01-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -20…120 °C
- Element type
- NTC10-01
- Nominal resistance
- 10 kΩ @25°C, Beta 3977
- Equivalent
- Aquatrol - Johnson Controls - Satchwell - Trend - Cylon - Honeywell - Distech
- Insertion length
- 90 mm
-
SI-NTC10-02-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -20…120 °C
- Element type
- NTC10-02
- Nominal resistance
- 10 kΩ @25°C, Beta 3435
- Equivalent
- Carel - Evco - Eliwell - AB Industrietechnik
- Insertion length
- 90 mm
-
SI-NTC10-03-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -20…120 °C
- Element type
- NTC10-03
- Nominal resistance
- 10 kΩ @25°C, Beta 3695
- Equivalent
- Andover - Delta Controls - Siebe - York
- Insertion length
- 90 mm
-
SI-NTC20-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -30…70 °C
- Element type
- NTC20
- Nominal resistance
- 20 kΩ @25°C, Beta 4262
- Equivalent
- Honeywell
- Insertion length
- 90 mm
-
SI-NI1000-01-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -20…120 °C
- Element type
- NI1000-01
- Nominal resistance
- 1000 Ω @0°C, TK5000
- Equivalent
- Siemens - Landis & Staefa
- Insertion length
- 90 mm
-
SI-NI1000-02-YImmersion sensor- Media temp limits
- -20…120 °C
- Measuring range, temp
- -30…70 °C
- Element type
- NI1000-02
- Nominal resistance
- 1000 Ω @0°C, TK6180
- Equivalent
- Sauter
- Insertion length
- 90 mm
Specifications
| Mounting | Immersion |
|---|---|
| Protection class | IP65 |
| Dimensions, external (WxHxD) | 78x158x104 mm, 78x263x104 mm |
| Weight, incl. packaging | 0.16 kg, 0.19 kg |
| Tube diameter | 5 mm |
| Mounting | Duct |
| Time constant | 4 s |
| Pressure rating immersion | PN16 |
| (Well/Pressure) connection | R 1/4 " |
| Cable gland | M16x1,5 |
| Terminal type | Screw Terminal |
| Detachable terminal | Yes |
| Terminal wire size | 1.5 mm² |
| Material, housing | Polycarbonate (PC) |
| Material tube | Stainless steel, EN 1.4301 (AISI 304) |
Software & documentation
Product sheet