TPDA25C Differential pressure transmitters with communication
Differential pressure transmitter with I/O modules for HVAC applications.
Navigate on this page
Specifications
Working range | 0…2500 Pa |
---|---|
Number of sensors | 1 |
Supply voltage | 24 V AC/DC ±15 % |
---|---|
Overall accuracy pressure | ≤ 1 % full scale |
Power consumption | 2 VA (rms), min. trafo size 7,5 VA |
Operating temperature | -25…+50°C |
Communication | EXOline / Modbus |
Protection class | IP54 |
PT1000 input | -40…+60°C / -40…+140°F, accuracy ±1 K (-25…0°C), ±0.5 K (0…50°C) |
Ni1000 input | -40…+60°C / -40…+140°F, accuracy ±1 K (-25…0°C), ±0.5 K (0…50°C) |
Digital input | Potential-free contacts on/off (closed=on) |
0...10 V input | ±1 % full scale accuracy |