Differential pressure transmitters with analogue outputs

Differential pressure transmitter for HVAC applications with one or two analogue outputs. The transmitter can be configured for output signals 0-10 V or 4…20 mA.

Navigate on this page

Articles

(5 st)
  • TPDA12A
    TPDA12A
    Working range
    0…1250 Pa
    Number of sensors
    1
  • TPDA25A
    TPDA25A
    Working range
    0…2500 Pa
    Number of sensors
    1
  • TPDA75A
    TPDA75A
    Working range
    0…7500 Pa
    Number of sensors
    1
  • TPDA1225A2
    TPDA1225A2
    Working range
    PS1: 0…1250 Pa
    Number of sensors
    2
  • TPDA1275A2
    TPDA1275A2
    Working range
    PS1: 0…1250 Pa
    Number of sensors
    2
Specifications for Differential pressure transmitters with analogue outputs
Supply voltage

24 V AC/DC ±15 %

Overall accuracy pressure ≤ 1 % full scale
Power consumption

0…10 V mode : 2 VA (rms), min. trafo size 7,5 VA

4…20 mA mode : 2.7 VA (rms), min. trafo size 9 VA

Operating temperature -25…+50°C
Protection class IP54