TV090UR85 Immersion thermostats, IP 54

Temperature control in pipes for heating, cooling and air conditioning systems, boilers and heaters. Temperature monitoring and safety protection with manual reset (2 stages).
Specifications for TV090UR85
Temperature range 1 0…90 °C
Temperature range 2 65…85 °C
Hysteresis
Step diff.
Max. bulb temperature 120 °C
Function manual maximum reset with SPDT contact
Hidden setpoint -
Specifications for Immersion thermostats, IP 54
Sensor element Copper bulb with 120 mm brass pocket
Contacts Microswitches with SPDT contacts (heat/cool)
Switch capacity With SPDT contact: NC 250 V AC 16 (6) A /NO 250 V AC 6 (4)
manual maximum reset: NC 250 V AC 16 (2,5) A / NO 250 V AC 0,5 A
Ambient temperature -35…+65°C
Ambient humidity 10...90 % RH (non-condensing)
Storage temperature -20…+70°C
Storage humidity < 95% RH
Casing Bayblend® base, ABS cover (2 stage models: sealed ABS)
Weight single stage: 440 g
double range: 560 g
Dimensions 108 x 70 x 72mm
Protection class IP54
Isolation class I
DBZ-30/14

Brass pocket 120 mm, ø external 8 mm, ø internal 7 mm, connection R 1/2"

DBZ-40/14

Brass pocket 108 mm, Ø external 16 mm, Ø internal 15 mm, connection R 1/2”

DBZ-31/14

Stainless steel pocket AISI 304, 120 mm, ø external 9 mm, ø internal 7 mm, connection R 1/2"

DBZ-41/14

Stainless steel AISI 304 pocket, 120 mm, Ø external 16 mm, Ø internal 15 mm, connection R 1/2”